![Omntec PROTEUS OEL8000III Series Manual Download Page 16](http://html1.mh-extra.com/html/omntec/proteus-oel8000iii-series/proteus-oel8000iii-series_manual_740737016.webp)
PROTEUS
OMNTEC
Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DE00014 DE00015 DE00020-10 rev2045.docx Page 16 of 71 Rev Date: 10-15-2021
Serial Interface Manual
OEL8000III Series Models K/X
Command: 10T Inventory Report
Command Format:
<S0H>10T
Typical Response Message:
<S0H>100MMDDHHmmsssTPssssIIIhhGGGGGGSFFFtGGGGGGWW(W)t.... (W) – see Note 10
TPssssIIIhhGGGGGGSFFFtGGGGGGWW(W)t9CCCC<ETX>
Notes:
1.
MMDDHHmm - Current Date and Time(month, day, hours, minutes)
2.
sss - Three system status characters:
a.
The first "s" is always ‘0’
b.
The second "s" is always ‘0’
c.
The third "s" is always ‘0’
3.
T - Tank Number (Decimal, 0 = all)
4.
P - Product code character (set by function 55T)
5.
ssss - Four tank status characters:
a.
The first "s" is "1" if the tank is "enabled"
b.
The second "s" is "1" if the tank is "enabled"
c.
The third "s" is unused (always 0)
d.
The fourth "s" is "1" if there is a delivery-in-progress
6.
IIIhh - Fuel level in inches and hundredths
7.
GGGGGG - Fuel volume in gallons
8.
SFFFt - Fuel temperature in degrees Fahrenheit and tenths with a preceding sign
character (0 or -)
9.
GGGGGG - Tank ullage in gallons
10. WWt - Water level in inches and tenths (Inches)
10. WWWt - Water level in inches and tenths (Millimeters)
11. 9 - Data Termination Flag
12. CCCC - Message Checksum