![Omntec PROTEUS OEL8000III Series Manual Download Page 36](http://html1.mh-extra.com/html/omntec/proteus-oel8000iii-series/proteus-oel8000iii-series_manual_740737036.webp)
PROTEUS
OMNTEC
Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DE00014 DE00015 DE00020-10 rev2045.docx Page 36 of 71 Rev Date: 10-15-2021
Serial Interface Manual
OEL8000III Series Models K/X
Command
: 205 In-Tank Status Report
Command Format:
Computer: <SOH>i205TT
Typical Response Message, Computer Format:
<SOH>i205TTYYMMDDHHmmTTnnAA...
TTnnAA...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. nn - Number of alarms (Hex, == = none)
4. AA – active Tank Alarm Type:
See explanation for ‘AA’ in function i101.
5. && - Data Termination Flag
6. CCCC - Message ChecksumCommand: