![Omntec PROTEUS OEL8000III Series Manual Download Page 35](http://html1.mh-extra.com/html/omntec/proteus-oel8000iii-series/proteus-oel8000iii-series_manual_740737035.webp)
PROTEUS
OMNTEC
Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DE00014 DE00015 DE00020-10 rev2045.docx Page 35 of 71 Rev Date: 10-15-2021
Serial Interface Manual
OEL8000III Series Models K/X
Command: 203 In-Tank Leak Detect Report
Command Format:
Computer: <SOH>i203TT
Typical Response Message, Computer Format:
<SOH>i203TTYYMMDDHHmmTTpYYMMDDHHmmHHNNFFFFFFFF...
TTpYYMMDDHHmmHHNNFFFFFFFF...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3. p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4. YYMMDDHHmm - Starting Date/Time
5. HH - Test Duration (hours)
6. NN - Number of eight character Data Fields to follow (Hex)
7. FFFFFFFF - ASCII Hex IEEE float:
1. Starting Temp
2. Ending Temp
3. Starting Volume
4. Ending Rate
8. && - Data Termination Flag