![Omntec PROTEUS OEL8000III Series Manual Download Page 17](http://html1.mh-extra.com/html/omntec/proteus-oel8000iii-series/proteus-oel8000iii-series_manual_740737017.webp)
PROTEUS
OMNTEC
Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DE00014 DE00015 DE00020-10 rev2045.docx Page 17 of 71 Rev Date: 10-15-2021
Serial Interface Manual
OEL8000III Series Models K/X
Command: 15T Delivery Report
Command Format:
<S0H>15T
Typical Response Message:
<S0H>150TPrrMMDDHHmmGGGGGGSFFFtMMDDHHmmGGGGGGSFFFt....
TPrrMMDDHHmmGGGGGGSFFFtMMDDHHmmGGGGGGSFFFt....9CCCC<ETX>
Notes
:
1. T - Tank Number (Decimal, 0 = all)
2. P - Product code character (set by function 55T)
3. rr - Number of delivery reports to follow for the tank. If it is 00, no
reports are included in the response for this tank
1.
MMDDHHmm – Starting Current Date and Time(month, day, hours, minutes).
2.
GGGGGG – Starting Fuel volume in gallons
3.
SFFFt – Starting Fuel temperature in degrees Fahrenheit and tenths with a
preceding sign character (0 or -)
7. MMDDHHmm – Ending Current Date and Time(month, day, hours, minutes).
8. GGGGGG – Ending Fuel volume in gallons
9. SFFFt – Ending Fuel temperature in degrees Fahrenheit and tenths
with a preceding sign character (0 or -)
10. 9 - Data Termination Flag
11. CCCC - Message Checksum