PROTEUS
OMNTEC
Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DE00014 DE00015 DE00020-10 rev2045.docx Page 30 of 71 Rev Date: 10-15-2021
Serial Interface Manual
OEL8000III Series Models K/X
04 = Tank Overfill Alarm
05 = Tank Low Product Alarm
06 = Tank Sudden Loss\Theft Alarm
07 = Tank High Product Alarm
09 = Tank Probe Out Alarm
11 = Tank Delivery Needed Warning
12 = Tank Maximum Level Alarm
- If AA is 03 and NN is:
00 = Sensor Normal
02 = Sensor Setup Data Warning
03 = Sensor Fuel Alarm
04 = Sensor Out Alarm
05 = Sensor Short Alarm
06 = Sensor Water Alarm
07 = Sensor Water Out Alarm
08 = Sensor High Liquid Alarm
09 = Sensor Low Liquid Alarm
10 = Sensor Liquid Warning
16 = Alarm
17 = Liquid Alarm
18 = Vapors Detected
19 = Level Alarm
20 = No Reply
21 = Bus No Reply
22 = Low Temp Alarm
23 = High Temp Alarm
24 thru 44 = Special Alarms (Contact OMNTEC)
5. TT - Tank/Sensor Number
6. SS - Alarm State
01 = Alarm cleared
02 = Alarm occurred
7. YYMMDDHHmm - Date/Time Alarm state occurred
8. && - Data Termination Flag
9. CCCC - Message Checksum