![Omntec PROTEUS OEL8000III Series Manual Download Page 32](http://html1.mh-extra.com/html/omntec/proteus-oel8000iii-series/proteus-oel8000iii-series_manual_740737032.webp)
PROTEUS
OMNTEC
Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DE00014 DE00015 DE00020-10 rev2045.docx Page 32 of 71 Rev Date: 10-15-2021
Serial Interface Manual
OEL8000III Series Models K/X
Command: 201 In-Tank Inventory Report
Command Format:
Display: <SOH>I20100
Computer: <SOH>i20100
Typical Response Message, Display Format:
<SOH>
I20100
JUL 28, 2013 11:41 PM
info
info
info
info
TANK PRODUCT VOLUME TC-VOLUME ULLAGE HEIGHT WATER TEMP
5 RED-DYED 2700.1 2676.0 7299.8 19.441 1.122 81.2
6 REGULAR,GAS 2700.1 2676.0 7299.8 19.441 1.122 81.2
<ETX>
Typical Response Message, Computer Format:
<SOH>
i
201TTYYMMDDHHmmTTpssssNNFFFFFFFF...
TTpssssNNFFFFFFFF...&&CCCC<ETX>
<SOH>
t
201TTYYMMDDHHmm
ss
TTpssssNNFFFFFFFF...
TTpssssNNFFFFFFFF...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
1a. YYMMDDHHmmss - Current Date and Time with seconds
2. TT - Tank Number (Decimal, 00 = all)
3. p - Product Code (single ASCII character, from 20 Hex - 7E Hex)
4. ssss - Tank Status Bits:
Bit 1 - (LSB) Delivery in Progress (Bit high 0001=In progress)
Bit 2 - Leak Test in Progress (Bit high 0002=In progress)
Bit 3 - Unused
Bit 4-16 – Unused
5. NN - Number of eight character Data Fields to follow (Hex)
6. FFFFFFFF - ASCII Hex IEEE float:
1. Volume
2. TC Volume
3. Ullage
4. Height
5. Water
6. Temperature
7. Water Volume
7. && - Data Termination Flag
8. CCCC - Message Checksum