![Omntec PROTEUS OEL8000III Series Manual Download Page 26](http://html1.mh-extra.com/html/omntec/proteus-oel8000iii-series/proteus-oel8000iii-series_manual_740737026.webp)
PROTEUS
OMNTEC
Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DE00014 DE00015 DE00020-10 rev2045.docx Page 26 of 71 Rev Date: 10-15-2021
Serial Interface Manual
OEL8000III Series Models K/X
Command: 101 System Status Report
Command Format:
Display: <SOH>I10100
Computer: <SOH>i10100
Typical Response Message, Display Format:
<SOH>
I10100
JUL 29, 2013 05:24 AM
info
info
info
info
SYSTEM STATUS REPORT
ID STATUS
T1 Normal
T3 Normal
T4 Normal
T5 Normal
T6 Normal
T7 Normal
T9 Normal
T10 Normal
T11 Normal
T12 Normal
S1 Normal
S2 Normal
S3 Normal
S17 Normal
<ETX>
Typical Response Message, Computer Format:
<SOH>i10100YYMMDDHHmmAANNTT....
AANNTT&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. AA - Alarm/Warning Category:
00 - All Functions Normal
01 - System Alarm
02 - Tank Alarm
03 - Liquid Sensor Alarm
21 – PLLD Alarm
60 – Volumetric Leak Test
3. NN - Alarm Type Number:
- If AA is 01 and NN is:
01 = Printer out of Paper