Command: OMNTEC 517 Inquire Individual System Units
Command Format:
Computer: <SOH>o51700
Typical Response Message, Computer Format:
<SOH>o51700YYMMDDHHmmVHT &&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. V – System Units: Volume
(0=Gallons, 1=Liters,
2=Barrels)
3.
H - System Units: Height
(0=inches, 1= millimeters, 2=Feet )
4.
T - System Units: Temperature (0=Fahrenheit, 1=Celsius)
5. && - Data Termination Flag
6. CCCC - Message Checksum