OEL8000III Series Models K/X
Command: PCL (Print CITLD Log)
Command Format:
PCL <enter>
Typical Response Message:
--CITLD REPORT 2.00
TANK 1 Diesel Fuel #2
Month: JUL, 2015
Pass Hours: 120.0
Test Height: 67.9%
Test Volume: 6741.78(Gal)
Slope: -0.009(Gal/hr)
.2(Gal/hr), Thresh .1 PASSED
TANK 1 Diesel Fuel #2
Month: AUG, 2015
Pass Hours: 105.0
Test Height: 67.9%
Test Volume: 6734.98(Gal)
Slope: -0.002(Gal/hr)
.2(Gal/hr), Thresh .1 PASSED