![Omntec PROTEUS OEL8000III Series Manual Download Page 31](http://html1.mh-extra.com/html/omntec/proteus-oel8000iii-series/proteus-oel8000iii-series_manual_740737031.webp)
PROTEUS
OMNTEC
Mfg., Inc., 2420 Pond Road, Ronkonkoma, NY 11779
Phone (631) 981-2001 Fax (631) 981-2007 www.OMNTEC.com
File Name: DE00014 DE00015 DE00020-10 rev2045.docx Page 31 of 71 Rev Date: 10-15-2021
Serial Interface Manual
OEL8000III Series Models K/X
Command: 112 Non-Priority Alarm History Report
Command Format:
Display:
<SOH>I11200
Computer:
<SOH>i11200
Typical Response Message, Display Format:
<SOH>
I11200
JUL 28, 2013 11:39 PM
info
info
info
info
NON-PRIORITY ALARM HISTORY
ID CATEGORY DESCRIPTION ALARM TYPE
STATE
DATE
TIME
SYSTEM
PAPER OUT
CLEAR
6-20-13
12:01PM
SYSTEM
PAPER OUT
ALARM
6-20-13
12:00PM
<ETX>
Typical Response Message, Computer Format:
<SOH>i11200YYMMDDHHmmAAccNNTTSSYYMMDDHHmm...
AAccNNTTSSYYMMDDHHmm&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. AA - Alarm/Warning Category:
See explanation for "AA" in Function i11100
3. cc - Sensor Category
See explanation for "cc" in Function i11100
4. NN - Alarm Type Number:
See explanation for "NN" in Function i11100
5. TT - Tank/Sensor Number
6. SS - Alarm State
01 = Alarm cleared
02 = Alarm occurred
7. YYMMDDHHmm - Date/Time Alarm state occurred
8. && - Data Termination Flag9. CCCC - Message Checksum
9. CCCC - Message Checksum