Serial Interface Manual
OEL8000III Series Models K/X
Command: 206 In-Tank Alarm History Report
Command Format:
Computer: <SOH>i20600
Typical Response Message, Computer Format:
<SOH>i206TTYYMMDDHHmmTTnnYYMMDDHHmmaaaa...
TTnnYYMMDDHHmmaaaa...&&CCCC<ETX>
Notes:
1. YYMMDDHHmm - Current Date and Time
2. TT - Tank Number (Decimal, 00 = all)
3.
nn - Number of alarms in history for tank (Decimal, 00 = none)
4. YYMMDDHHmm - Date and time alarm occurred
5. aaaa - Type of alarm: (Hex)
0003 = Tank High Water Alarm
0004 = Tank Overfill Alarm
0005 = Tank Low Low Product Alarm
0006 = Tank Sudden Loss Alarm
0007 = Tank High High Product Alarm
0009 = Tank Probe Out Alarm
000B = Tank Delivery Needed Warning
6. && - Data Termination Flag
7. CCCC - Message Checksum