Page: 109
5. Calibration
Tips & Warnings
It is not recommended that calibration be performed until the process
is fully understood.
5.1. Voltage and Current Calibration
Analog Input Calibration Requirement for
OME-ET-7000/OME-PET-7000
Connect the calibration voltage/current source to channel 0 and only the channel
0 should be enabled during calibration.
Type Code
The following table shows all of the type code for use in voltage and current, you can
use it upon the model number of OME-ET-7000/OME-PET-7000 (e.g. OME-ET-7017
can use type 07 ~ 1A).
Type Code
00
01
02
03
04
05
06
07
Zero Input
0 mV
0 mV
0 mV
0 mV
0 V
0 V
0 mA
0mA
Span Input +15 mV +50 mV +100 mV +500 mV
+1 V
+2.5 V +20 mA +20 mA
Type Code
08
09
0A
0B
0C
0D
1A
Zero Input
0 V
0 V
0 V
0 mV
0 mV
0 mA
0 mA
Span Input
+10V
+5 V
+1 V
+500 mV +150 mV +20 mA +20 mA
The following steps will show you how to calibrate the OME-ET-7017 (8 AI, 4 DO):
Step 1
Κ
Κ
Warm up the module for 30 minutes.
Step 2
Κ
Enable the channel 0 to calibrate and disable other channels.
Please go to the configuration page of Modules I/O Settings (refer to Section
3.2.3), set AI0 as ON and the others as OFF. (As figure below)
Summary of Contents for OME-ET-7000 Series
Page 1: ......
Page 2: ......
Page 37: ...Page 32 The lower section of the page provides a brief introduction to the web interface...
Page 86: ...Page 81 After completing the configuration click the Submit button to save the settings 1 2...
Page 92: ...Page 87 The default URL that the More Information item will link to http www omega com...
Page 158: ......
Page 159: ......