Page: 146
Type Code
Input Range
Data Format
+F.S
-F.S
14
Type B
Thermocouple
0 ~ 1820°C
Engineering Unit
+18200
0
2’s comp HEX
7FFF
0000
15
Type N
Thermocouple
-270 ~ 1300°C
Engineering Unit
+13000
-2700
2’s comp HEX
7FFF
E56B
16
Type C
Thermocouple
0 ~ 2320°C
Engineering Unit
+23200
0
2’s comp HEX
7FFF
0000
17
Type L
Thermocouple
-200 ~ 800°C
Engineering Unit
+8000
-2000
2’s comp HEX
7FFF
E000
18
Type M
Thermocouple
-200 ~ 100°C
Engineering Unit
+10000
-20000
2’s comp HEX
4000
8000
19
Type L
DIN43710
Thermocouple
-200 ~ 900°C
Engineering Unit
9000
-2000
2’s comp HEX
FFFF
E38E
20
Platinum 100
α
=0.00385
-100 ~ 100°C
Engineering Unit
+10000
-10000
2’s comp HEX
7FFF
8000
21
Platinum 100
α
=0.00385
0 ~ 100°C
Engineering Unit
+10000
0
2’s comp HEX
7FFF
0000
22
Platinum 100
α
=0.00385
0 ~ 200°C
Engineering Unit
+20000
0
2’s comp HEX
7FFF
0000
23
Platinum 100
α
=0.00385
0 ~ 600°C
Engineering Unit
+6000
0
2’s comp HEX
7FFF
0000
Summary of Contents for OME-ET-7000 Series
Page 1: ......
Page 2: ......
Page 37: ...Page 32 The lower section of the page provides a brief introduction to the web interface...
Page 86: ...Page 81 After completing the configuration click the Submit button to save the settings 1 2...
Page 92: ...Page 87 The default URL that the More Information item will link to http www omega com...
Page 158: ......
Page 159: ......