Page: 144
Appendix D. Analog Input Type and Data Format Table
Type Code
Input Range
Data Format
+F.S
-F.S
00 -15
~
+15 mA
Engineering Unit
+15000 -15000
2’s comp HEX
7FFF 8000
01
-50 ~ +50 mA
Engineering Unit
+5000
-5000
2’s comp HEX
7FFF
8000
02
-100 ~ +100 mV
Engineering Unit
+10000 -10000
2’s comp HEX
7FFF 8000
03
-500 ~ +500 mV
Engineering Unit
+5000
-5000
2’s comp HEX
7FFF
8000
04 -1
~
+1
V
Engineering Unit
+10000 -10000
2’s comp HEX
7FFF 8000
05
-2.5 ~ +2.5 V
Engineering Unit
+25000
-25000
2’s comp HEX
7FFF
8000
06 -20
~
+20 mA
Engineering Unit
+20000 -20000
2’s comp HEX
7FFF 8000
07
+4 ~ +20 mA
Engineering Unit
+20000
+4000
2’s comp HEX
FFFF
0000
08 -10
~
+10 V
Engineering Unit
+10000 -10000
2’s comp HEX
7FFF 8000
09
-5 ~ +5 V
Engineering Unit
+5000
-5000
2’s comp HEX
7FFF
8000