Page: 83
3.5.2. Example 2: Pair Connection - DO to DI
In this example, we will show how to use this feature to achieve DI/DO mapping on
two remote I/O devices.
Hardware devices:
OME-PET-7026 (AIO/DIO module), OME-PET-7044 (DIO module), PoE Switch, and
Power Supply (48 V).
Hardware Connections:
Software Configuration:
The following provides step-by-step instructions for how to configure the
OME-ET-7000/OME-PET-7000 via the built-in web interface.
In this example, the DO0/DO1 of the OME-PET-7026 must be mapped to the
DI0/DI1 of the OME-PET-7044. Later, when the status of the DI0/DI1 is switched to
ON, the status of the DO0/DO1 will be switched to logic high automatically.
OME-PET-7044
PoE
Switch
OME-PET-702
6
Power Supply
48 V