C.2. Power-on Value
Many industrial applications require a "safe" start-up condition to prevent accidents at
critical points in the process. Each OME-ET-7000/OME-PET-7000 contains an initial
power-on value which is used to configure the analog/digital outputs on power up. In
other words, power-on value can be considered as a start-up value. The power-on
value is loaded into the output modules under 3 conditions: power on, reset by
Module Watchdog, reset by the reset command.
User can set the power-on value of the specific analog/digital output channel and the
power-on value is stored in EEPROM.
Setting the Power-on Value for a Specific Digital Output Channel
Step 1
Κ
Κ
Log into the OME-ET-7000/OME-PET-7000 web page, and then click the
“
Module I/O Settings
” option in the “
Configuration
” section of the Main Menu
Step 2
Κ
Enable the Power-on Value
by checking the “
ON
” radio button
Step 3
Κ
Click the
“
Submit
”
button to complete the configuration of the power-on
Value