Page: 84
Step 1
Κ
Κ
Log in to the OME-PET-7026 web interface
Enter the IP address of the OME-PET-7026 in the browser, and then
enter your user name and password to log in to the OME-PET-7026
web interface. Refer to chapter 3
“
Web Applications
”,
for more
details.
Step 2
Κ
Configure the Modbus Settings for the OME-PET-7026
Click the “Pair Connection” option in the Main Menu
, and enter the
details listed in the table below into the respective fields.
Field
Settings
I/O Pair Connection
Select this option to enable the I/O pair connection
functions.
Remote IP Address
This is the IP address of the OME-PET-7044 (e.g.
192.168.1.99)
Remote TCP Port
502
Connection Timeout
3000 ms
Reconnect Interval
5000 ms
Remote Net ID
1 (Default = 1, the Net ID for the OME-PET-7044)
To
determine the Net ID, check the “
Modbus Definition
” section on the
“
Common Function
” page, which can be found by clicking the “
Module I/O
Settings
” option in the “
Configuration
” section of the Main Menu.
Scan Time
300 ms
Access Type
Select DO
Local DO Base
Address
0, (Starting from DO0 on the OME-PET-7026)
Remote DI Base
Address:
0, (Starting from DI0 on the OME-PET-7044)
I/O Count
2, (Using DO0, DO1 and DI0, DI1)
Communication
Timeout
400 ms
Summary of Contents for OME-ET-7000 Series
Page 1: ......
Page 2: ......
Page 37: ...Page 32 The lower section of the page provides a brief introduction to the web interface...
Page 86: ...Page 81 After completing the configuration click the Submit button to save the settings 1 2...
Page 92: ...Page 87 The default URL that the More Information item will link to http www omega com...
Page 158: ......
Page 159: ......