Page: 112
Step 5
Κ
Κ
Apply the zero calibration voltage/current to channel 0.
In this example, we use type code - 09 and its
“Zero Input” is 0 V.
Type Code
09
Input Range -5V ~ +5 V
Step 6
Κ
Send the zero calibration command.
Double-click on address 831 to set it as ON. If the calibration is successful,
the value will return 0.
Step 7
Κ
Apply the span calibration voltage/current to channel 0.
In this example, we use type code - 09 and its
“Span Input” is +5 V.
Type Code
09
Input Range -5V ~ +5 V