32
TABLE 3-4 (Cont'd)
FUNCTION
.16 (Cont'd) INPUT SENSOR SELECT & RANGE TABLE
.17 NEGATIVE TEMPERATURES
Allows for activation of second setpoint. Refer to Second Output
Operation, Section 3.11. Note that in ON/OFF mode, SP2 can act
as a deviation alarm from the first setpoint. It can be set as a high
deviation, low deviation, or either high or low deviation (out of
bounds).
LINEAR PROCESS INPUTS (SEE SECTION 3.10)
(Op#).(Fn#)
Input
Display
11.16
0-20 mV
0-100
12.16
4-20 mV
0-100
13.16
0-20 mV
0-1000
14.16
4-20 mV
0-1000
15.16
0-20 mV
0-2000
Must be enabled to allow negative temperatures to be measured
(using either T thermocouple or RTD only).
(Op#).(Fn#) Parameter/Comment
0.17
Disabled
1.17
Enabled
.18 DISPLAY RESOLUTION (1 OR 0.1 DEGREE)
Allows selection of 0.1° resolution over limited temperature range
(-199.9 to + 199.9). Note: this affects other selections, such as
setpoint. Settings in 1° increments become 0.1° when Option 1 is
selected.
(Op#).(Fn#)
Parameter/Comment
0.18
Normal (1°)
1.18
High (tenth deg) Resolution (0.1°):
-199.9° to + 199.9
.19 SETPOINT 2 OPERATION SELECTION