29
TABLE 3-4 (Cont'd)
FUNCTION
.10 (Cont'd) CYCLE TIME/ON-OFF (OUTPUT 2)
Op#).(Fn#)
SP2 Proportional SP2 Hysteresis in
Band/Gain
ON/OFF mode
(Deadband)
0.11
2.5% x range
1.25%
1.11
0.5% x range
0.25%
2.11
1% x range
0.5%
3.11
2% x range
1%
4.11
3% x range
1.5%
5.11
5% x range
2.5%
6.11
10% x range
5%
7.11
20% x range
10%
8.11
1.5% x range
0.75%
9.11
4% x range
2%
10.11
6% x range
3%
11.11
7% x range
3.5%
12.11
8% x range
4%
13.11
14% x range
7%
14.11
100% x range
50%
(Op#).(Fn#) Parameter/Comment
4.10
20 sec
5.10
60 sec
6.10
Not Used
7.10
30 sec
*8.10
2 sec
*9.10
3 sec
*10.10
7 sec
11.10
14 sec
12.10
45 sec
Non-linear ranges for Cool Strategy:
13.10
0.15-10 sec
14.10
0.15-20 sec
15.10
0.06-15 sec
*not recommended with mechanical relay
.11 PROPORTIONAL BAND/DEADBAND (OUTPUT 2)
Set similarly to first setpoint Proportional Band (Function .5).