SELA U 24 75

Technical information and operating instructions

SE

C

_4

8

8

3

 05

.2

1

+44 (0)1543 443060 

[email protected] 

www.secontrols.com

Please keep these operating instructions for future reference and maintenance. 

Subject to technical modifi cations. Diagram is not binding.

Application

• 

24V DC Chain Motor.

• 

Environmental and Smoke Ventilation 

applications

• 

Range of Fixing Systems.

• 

       Marked

• 

Tested to principles of EN1210-2: 2003 

Annex G

Summary of Contents for SELA U 24 75

Page 1: ... com www secontrols com Please keep these operating instructions for future reference and maintenance Subject to technical modifications Diagram is not binding Application 24V DC Chain Motor Environmental and Smoke Ventilation applications Range of Fixing Systems Marked Tested to principles of EN1210 2 2003 Annex G ...

Page 2: ...V dc Amp Draw Current with load 1A Stroke 180 350 550 750 1000mm Operating Speed 8mm s Ambient Operating Temp 10 C 40 C Thrust Force 750N Close Force 650N Switching Electronic Limit Standard Finish Silver Adonised Rack White Motor Flex Length 1 5 MTR Flex Type 2 core 0 75mm Silicon Flex Colour White Product Warranty 10 000 strokes Duty Cycle 22 2 mins on 7 mins off Protection Degree IP55 Bracket En...

Page 3: ...ch attention must be paid All actuator products contain metallic plastic and electronic parts Redundant electronic products are classified as hazardous waste under the WEEE regulations Waste Electrical and Electronic Equipment Electronic parts must be disposed by an authorised and licensed recycler Handling and storage Care must be taken in transportation to the installation location and during fitt...

Page 4: ... of the cables in relation to the cable lengths and power consumption Care must be taken to ensure that actuator products are controlled with compatible products refer to SE Controls No liability will be accepted and no guarantee nor service is granted if actuator controls are used without such compatibility being confirmed Installation of this equipment must only be carried out by authorised compe...

Page 5: ...g All smoke ventilation systems must be periodically annually checked serviced maintained and if necessary repaired and re tested by a authorised trained and competent safety conscious persons Maintenance shall be carried out in accordance with the requirements of In order to keep the equipment in optimum operating condition it is recommended that ventilation systems are similarly maintained There...

Page 6: ...straight alignment between sliding bracket and eyebolt to ensure correct operation Close stroke position is adjusted by use of the threaded 6mm eyebolt if required Pivot Bracket ABU0040235F 4 Front Rear Pivot Bracket 2 Adjustable Eyebolt 3 Trunnion Bracket 6 Trunnion Bracket Front or rear pivot bracket kit allows bracket 4 to be secured to the actuator through the holes located either side of the ...

Page 7: ...radley Park Lichfield Staffordshire WS13 8RZ Company No 01468061 Vat No 377 5600 30 SE Controls is a Registered Trademark Lancaster House Wellington Crescent Fradley Park Lichfield Staffordshire WS13 8RZ Creating a healthier safer environment 44 0 1543 443060 sales secontrols com www secontrols com ...