17
Press and hold in
★
Repeatedly press
to increase value
(while pressing
★
) Repeatedly press
to decrease value
(while pressing
★
).
Release
★
(and stop pressing
or
button).
Press the P button. The temperature is now displayed. The
upper limit of the allowable setpoint has now been changed.
The new allowable setpoint range can be checked by repeating
Steps 1, 2, 3.
Steps 1-6 are repeated in Section 3.5.1.3 for your convenience.
To change the setpoint
to the desired value, press
★
and
hold in.
Press
or
to change the setpoint to the new value.
Release the
★
button. The temperature is now displayed.
Press the
★
button to check the setpoint value.
4.
5.
6.
7.
8.
9.
10
Note:
If the Default setpoint range maximum is not suitable, it can
be increased or decreased to any desired value within the
linearized band
Fn .16
Min/Max
Option
Type
°C
°F
1 J
Iron-Constantan
0-400
32-800
2
K
CHROMEGA
®
ALOMEGA
®
0-400
32-800
3 N
Nicrosil-Nisil
0-400
32-800
4
R
Pt-13% Rh/Pt
0-1600
32-1999
5
S
Pt-10% Rh1Pt
0-1600
32-1999
6
T
Copper-Constantan
0-250
32-500
7
E
CHROMEGA
®
-Constantan
0-500
32-1000
8
J DIN
Iron-Constantan
0-400
32-800
9
Pt100
100 Pt
RTD(
=0.00385)
0-200
32-400
10
B
Pt-30% Rh/Pt-6% Rh
0-1600
32-1999
TABLE 3-3
SENSOR DEFAULT SETPOINT RANGE TABLE
NOTE
If an attempt is made to set the setpoint outside of the setpoint
range, the setpoint will be at the end of the range.