31
Allows quick reset of all Functions to Default settings. Only
Function .22 (°C/°F) and Function .9 (Sensor Offset) will not
be reset. NOTE: 'Hidden' Function 15/Option 5 resets all functions,
except Function .22.
TABLE 3-4 (Cont'd)
FUNCTION
.15 RESETTING FUNCTION'S .0 -.24 TO DEFAULT SETTINGS
Op.Fn Sensor
Default Range
Linearized Range
Type °C
°F
°C
°F
1.16
J
0 to 400
32 to 800
0 to 800
32 to 1470
2.16
K
0 to 400
32 to 800
0 to 1200
32 to 1999
3.16
N
0 to 400
32 to 800
0 to 1200
32 to 1999
4.16
R
0 to 1600
32 to 1999
0 to 1600
32 to 1999
5 16
S
0 to 1600
32 to 1999
0 to 1600
32 to 1999
6.16
T
0 to 250
32 to 500
-199 to 250
-199 to 480
7.16
E
0 to 500
32 to 1000
0 to 600
32 to 1110
8.16
J-DIN
0 l0 400
32 to 800
0 to 800
32 to 1470
9.16
Pt100
0 to 200
32 to 400
-199 to 400
-199 to 750
10.16
B
0 to 1600
32 to 1999
0 to 1800
32 to 1999
(Options cont'd on next page)
NOTE
Range adjustments (including Default) only limit
setpoint values. Process temperatures will be
displayed over the full linearized range.
Selects thermocouple type or RTD. This is the first selection that
must be made for the unit to be used. NOTE: If 3-wire RTD
configuration is ordered, the Pt-100 (Option 9) must be selected.
Option 0 causes the CN9000A to "lock up" (another Option must
be selected to "bring the CN9000A back to life").
.16 INPUT SENSOR SELECT & RANGE TABLE
(Op#).(Fn#)
Parameter/Comment
0.15 Normal
1.15
Reset (Functions .22 and .9 will not reset)
5.15
Resets all functions except Function .22