59
Change to Function .4:
Change to Option Mode:
Change to Option 7:
Return to Operating Mode
STEP
ACTION
DISPLAY
3
4
5
6
7
8
Press
four times
Flashing
Press
★
Flashing
Press
seven times
Flashing
Press P
0.
4
7.
4
0.
4
CONTROL MAY NOW BE WORSE-TEMPERATURE WILL
SWING ABOVE AND BELOW SETPOINT.
Observe this swing carefully and record the difference between the
highest and the lowest reading (A =________) and time in
seconds between consecutive highest readings (T=________)
Locate your sensor in the table below to obtain a sensor factor and
use this with value for A to calculate size of "Proportioning Band"
(Function .5).
Use calculated % value for "Programming Band" width to select
option number in Function .5 table below. When between fixed
values choose next larger option.
Ax3
Sensor Factor
Sensor
Type
Pt100
RTD
Sensor
Factor
4
5
10
32
8
J, K, N, Fe Const.
THERMOCOUPLE TYPES
R, S, and B
E
T
%