44
Figure 3-2. Parameter Lock Positions
TABLE 3-6 (Cont'd)
FUNCTION
.46 READ QUARTER CYCLE TIME 1
.47 READ QUARTER CYCLE TIME 2
.48 READ QUARTER CYCLE TIME 3
.49 READ QUARTER CYCLE TIME 4
.50 (Not used)
Press
to go to Function .0.
3.13 PARAMETER LOCK
Measured in seconds, minimum of 2 seconds, maximum of 1800
seconds (30 minutes).
Measured in seconds, minimum of 2 seconds, maximum of 1800
seconds (30 minutes).
Measured in seconds, minimum of 2 seconds, maximum of 1800
seconds (30 minutes).
Measured in seconds, minimum of 2 seconds, maximum of 1800
seconds (30 minutes).
The chosen Parameters may be mechanically locked into memory
by removing or altering the position of the jumper behind the lower
front bezel (refer to Figure 3-2). Note that locked positions (2) and
(3) are alternatives and that the jumper socket is in the "inactive"
or locked position in (2). When the Parameter Lock has been
applied, only the Set-Up adjustments listed below are possible
(depress the P key):
1. Adjust Manual Reset (PD, P and ON/OFF modes only)-refer to
Section 3.6.2 for key sequences.
2. Adjust the second setpoint (assuming Function .19, either
Options 1, 2 or 3 have been selected).
3. Lock the main setpoint to prevent adjustment by the operator.
Jumper
Parameter Setting Position (1)
(Factory set in unlocked position)
Locked Position (2)
Locked Position (3)