Declared heating capacity and coefficient of performance at an indoor
temperature of 20 °C and outdoor temperature of T
j
, space heating
Heat pump model
EMi
22
EMi
22P
EMi
28
EMi
28P
EMi
43
EMi
43P
T
j
= –7 °C
kW/COPd
20.8/3.36
26.6/3.18
43.2/3.35
T
j
= +2 °C
kW/COPd
21.1/3.86
27.5/3.65
44.0/3.87
T
j
= +7 °C
kW/COPd
21.7/4.12
27.8/3.92
44.7/4.16
T
j
= +12 °C
kW/COPd
22.0/4.42
28.6/4.26
45.3/4.50
T
j
= bivalent
temperature
kW/COPd
20.7/3.16
26.8/3.10
42.8/3.22
Average climate
conditions
T
j
= operating
limit temperature
kW/COPd
20.7/3.16
26.8/3.10
42.8/3.22
T
j
= +2 °C
kW/COPd
20.7/3.16
26.8/3.10
42.8/3.22
T
j
= +7 °C
kW/COPd
21.4/3.53
27.3/3.35
44.0/3.55
T
j
= +12 °C
kW/COPd
21.8/4.15
28.3/3.99
44.9/4.20
T
j
= bivalent
temperature
kW/COPd
20.7/3.16
26.8/3.10
42.8/3.22
Warmer climate
conditions
T
j
= operating
limit temperature
kW/COPd
20.7/3.16
26.8/3.10
42.8/3.76
T
j
= –7 °C
kW/COPd
21.2/3.77
27.1/3.57
44.1/3.22
T
j
= +2°C
kW/COPd
21.6/4.18
28.1/3.96
45.0/4.20
T
j
= +7 °C
kW/COPd
22.3/4.43
28.5/4.22
45.8/4.48
T
j
= +12 °C
kW/COPd
22.6/4.56
29.3/4.42
46.4/4.67
T
j
= bivalent
temperature
kW/COPd
20.7/3.16
26.8/3.10
42.8/3.22
Colder climate
conditions
T
j
= operating
limit temperature
kW/COPd
20.7/3.16
26.8/3.10
42.8/3.22
Degradation coefficient, T
j
= –7 °C
C
dh
1.0
Bivalent temperatures, space heating
Heat pump model
EMi
22
EMi
22P
EMi
28
EMi
28P
EMi
43
EMi
43P
Average
T
bivalent
°C
–10
Warmer
T
bivalent
°C
–22
Colder
T
bivalent
°C
+2
Operating limit temperatures, space heating
Heat pump model
EMi
22
EMi
22P
EMi
28
EMi
28P
EMi
43
EMi
43P
Average
TOL
°C
–10
Warmer
TOL
°C
–22
Colder
TOL
°C
+2
72 (75)
M8010 2204EN
Summary of Contents for ESi 6-17
Page 2: ......
Page 62: ...Dimensional drawings ESi 10ESI14_2 ESI 1 ver 1 10ESI14_2 ESI 2 ver 1 60 75 M8010 2204EN...
Page 63: ...Dimensional drawings EMi 10EMI28T_3 EMI ver 1 M8010 2204EN 61 75...
Page 64: ...Dimensional drawings ELi 10ELI60T_2 ELI ver 1 62 75 M8010 2204EN...
Page 78: ...76 75 M8010 2204EN...
Page 79: ......