Maximum length of brine circuit loop, ESi 6–17
Heat pump
ESi 6
ESi 9
ESi 11
ESi 14
ESi 17
Borehole, PEH, PN6
m
500
350
450
–
–
1 brine circuit*
Horizontal loop,
PEM, PN10
m
450
300
–
–
–
Borehole, PEH, PN6
m
–
900
1200
900
600
2 brine circuits*
Horizontal loop,
PEM, PN10
m
–
750
1050
650
500
*Theoretical length with nominal flow, ΔT=4K. The actual pressure loss must be determined based on
local conditions.
The maximum number of brine circuits is 2.
Maximum length of brine circuit loop, EMi 22–43, ELi 60 and ELi 90
Heat pump
EMi 22
EMi 28
EMi 43
ELi 60
Eli 90
Borehole, PEH, PN6
m
–
–
–
–
–
1 brine circuit*
Horizontal loop,
PEM, PN10
m
–
–
–
–
–
Borehole, PEH, PN6
m
1050
–
–
–
–
2 brine circuits*
Horizontal loop,
PEM, PN10
m
900
–
–
–
–
Borehole, PEH, PN6
m
–
700
–
–
–
3 brine circuits*
Horizontal loop,
PEM, PN10
m
–
550
–
–
–
Borehole, PEH, PN6
m
–
–
750
900
–
4 brine circuits*
Horizontal loop,
PEM, PN10
m
–
–
600
700
–
Borehole, PEH, PN6
m
–
–
–
–
900
7 brine circuits*
Horizontal loop,
PEM, PN10
m
–
–
–
–
750
*Theoretical length with nominal flow, ΔT=4K. The actual pressure loss must be determined based on
local conditions.
6.6 Heating circuits
Heating circuit or circuits, ESi
In EMi and ELi models, the heating circuit pump is provided as an
optional accessory.
M8010 2204EN
67 (75)
Summary of Contents for ESi 6-17
Page 2: ......
Page 62: ...Dimensional drawings ESi 10ESI14_2 ESI 1 ver 1 10ESI14_2 ESI 2 ver 1 60 75 M8010 2204EN...
Page 63: ...Dimensional drawings EMi 10EMI28T_3 EMI ver 1 M8010 2204EN 61 75...
Page 64: ...Dimensional drawings ELi 10ELI60T_2 ELI ver 1 62 75 M8010 2204EN...
Page 78: ...76 75 M8010 2204EN...
Page 79: ......