Summer functions ver. 1
1. To activate the summer function, check the
Summer Function
checkbox.
2. Check the checkboxes for the heating circuit pumps that will not be used in the
summer. This will allow you to leave the circulation pumps on where they are
needed (in a heating circuit reserved for wet areas, for example).
3. Specify the start month for the summer period with the plus and minus buttons.
4. Specify the end month for the summer period with the plus and minus buttons.
5. Specify the minimum temperature at which the summer function will be active by
tapping the
Function min temperature
field.
4.6.5 Magna geo control: brine circuit pump settings
When commissioning the heat pump, the flow rate of the brine circuit pump can be
adjusted.
1. Use the
Brine pump speed
slider to adjust the flow rate as a percentage of the
maximum.
●
At 0%, the pump will be stopped.
●
At 1%, the flow rate will be at its lowest.
●
At 100%, the flow rate will be at its highest.
●
Factory setting: 90–100%.
The selected percentage value will be shown next to the slider.
4.6.6 Extra heat settings: control for external heat sources
These options apply only to configurations where an external heat
source is used in parallel with the heat pump.
By default, the heat pump can control one supplementary external heat source. The
number can be increased to 4 with an additional control module.
Extra heat settings ver. 1
40 (75)
M8010 2204EN
Summary of Contents for ESi 6-17
Page 2: ......
Page 62: ...Dimensional drawings ESi 10ESI14_2 ESI 1 ver 1 10ESI14_2 ESI 2 ver 1 60 75 M8010 2204EN...
Page 63: ...Dimensional drawings EMi 10EMI28T_3 EMI ver 1 M8010 2204EN 61 75...
Page 64: ...Dimensional drawings ELi 10ELI60T_2 ELI ver 1 62 75 M8010 2204EN...
Page 78: ...76 75 M8010 2204EN...
Page 79: ......