6 Technical data
6.1 Technical data
The performance between different units may vary. This variation is due to a wide
number of factors, such as the properties of the fluids used in the circuits, fouling of the
heat transfer surfaces in the condenser and evaporator circuit, flow rates, individual
differences between compressors (standard EN 12900) as well as refrigerant circuit
charge and adjustments made to the refrigerant circuit during installation.
ESi 6–17
Heat pump
ESi 6
ESi 9
ESi 11
ESi 14
ESi 17
Weight
kg
174
178
192
202
210
Compressor type
Scroll
Refrigerant
R407C
Refrigerant charge
g
1400
1900
2000
2500
2600
Compressor oil
POE
Condenser pump speed control
Constant curve mode 2
Constant curve mode 3
Desuperheater circuit
factory setting
%
35
40
Noise level @ 0/55 °C*
dB
37
40
41
Temperature limits,
brine/water
°C
–10/+60, +15/+30
Pressure limits, refrigerant
bar
1.5/29
*Tested in accordance with ISO 3744/2010, test point: B0/W55.
EMi 22–43, ELi 60, and ELi 90
Heat pump
EMi 22
(22P)
EMi 28
(28P)
EMi 43
(43P)
ELi 60
(60P)
ELi 90
(90P)
Weight
kg
395 (387)
395 (387)
420 (412)
515 (505)
605 (595)
Compressor type
Scroll
Refrigerant
R407C
R410A
Refrigerant charge
g
4900 (4700) 5000 (4800) 5900 (5700) 8700 (8500)
10000
(9800)
Compressor oil
POE
Condenser pump speed control
Constant curve mode 3
Desuperheater
circuit factory setting
%
55 (–)
57 (–)
85 (–)
Noise level @ 0/55 °C*
dB
45
46
49
60
65
Temperature limits,
brine/water
°C
–10/+60,
+15/+30
–10/+60,
+20/+30
Pressure limits, refrigerant
bar
1.5/29
4/45
*Tested in accordance with ISO 3744/2010, test point: B0/W55.
58 (75)
M8010 2204EN
Summary of Contents for ESi 6-17
Page 2: ......
Page 62: ...Dimensional drawings ESi 10ESI14_2 ESI 1 ver 1 10ESI14_2 ESI 2 ver 1 60 75 M8010 2204EN...
Page 63: ...Dimensional drawings EMi 10EMI28T_3 EMI ver 1 M8010 2204EN 61 75...
Page 64: ...Dimensional drawings ELi 10ELI60T_2 ELI ver 1 62 75 M8010 2204EN...
Page 78: ...76 75 M8010 2204EN...
Page 79: ......