ID
Analog input
B1
Hot gas 1
B2
Not in use
B3
Storage tank upper section
B4
Storage tank lower section
B5
Outdoor temperature
ID
Analog input
B6
Heating circuit 1 temperature
B7
Heating circuit 2 temperature
B8
Heating circuit 3 or DHW temperature
B9
Not in use
B10
Brine circuit temperature
Analog outputs
Analog output states ver. 1
ID
Analog output
Y1
Heating circuit 1 valve
Y2
Heating circuit 2 valve
Y3
Analog 0–10 V, immersion heater
ID
Analog output
Y4
Heating circuit 3 / DHW valve
Y5
Brine circuit pump
Y6
Desuperheater valve
5.4.3 Running information
The
Running information
view shows the compressor’s current status, such as OFF
or ON.
5.4.3.1 Heating circuit amount: the number of heating circuits
The
Heating circuit amount
view allows you to select the number of heating circuits
connected to the heat pump.
There can be 1-3 heating circuits; circuits 2 and 3 are optional accessories. If all three
heating circuits are in use, the
Domestic hot water limiter
function (see
Hot water
temperature limiter
and
Storage tank settings
) cannot be active.
5.4.4 Hot water temperature limiter
Use this view to activate the Hot water limiter function (optional accessory). This
function prevents domestic hot water temperature from reaching hazardous levels.
The view allows you to change the input for domestic hot water temperature sensor
and the output for the associated control valve (
position valve
).
● The standard setting for the DHW temperature sensor is B8.
● The standard setting for the analog control signal is is Y4.
M8010 2204EN
51 (75)
Summary of Contents for ESi 6-17
Page 2: ......
Page 62: ...Dimensional drawings ESi 10ESI14_2 ESI 1 ver 1 10ESI14_2 ESI 2 ver 1 60 75 M8010 2204EN...
Page 63: ...Dimensional drawings EMi 10EMI28T_3 EMI ver 1 M8010 2204EN 61 75...
Page 64: ...Dimensional drawings ELi 10ELI60T_2 ELI ver 1 62 75 M8010 2204EN...
Page 78: ...76 75 M8010 2204EN...
Page 79: ......