Seasonal performance factor, EMi 22–43, ELi 60 and ELi 90
Heat pump
EMi 22
EMi 28
EMi 43
ELi 60
Eli 90
Domestic hot water
SPF
dhw
0/35
3.61
3.66
3.61
3.73
3.62
SPF
spaces
0/35
4.49
4.56
4.50
4.64
4.51
SPF
spaces
0/45
3.61
3.66
3.61
3.73
3.62
SPF
spaces
0/55
3.04
3.09
3.05
3.14
3.06
Space heating
SPF
spaces
0/60
2.83
2.88
2.84
2.93
2.84
Seasonal performance factors in accordance with he National Building Code of Finland.
6.5 Brine circuits
Pump data, ESi 6–17
Heat pump
ESi 6
ESi 9
ESi 11
ESi 14
ESi 17
Pump’s energy class
A (variable frequency drive)
Pump’s nominal input power
W
5–89
10–170
Pump speed, factory setting
%
90
Flow, ΔT=3K*
l/s
0.64
0.79
0.94
1.18
1.34
Maximum allowed external pressure loss,
ΔT=3K*
kPa
53
48
81
65
54
Flow, ΔT=4K*
l/s
0.48
0.59
0.70
0.89
1.00
Max. allowed external pressure loss, ΔT=4K* kPa
63
55
96
80
70
*ISO 14511.
Pump data, EMi 22–43, ELi 60 and ELi 90
Heat pump
EMi 22
EMi 28
EMi 43
ELi 60
Eli 90
Pump’s energy class
A (variable frequency drive)
Pump’s nominal input power
W
160–1330
30–2100
Pump speed, factory setting
%
90
100
Flow, ΔT=3K*
l/s
1.65
2.19
3.41
4.52
6.72
Maximum allowed external pressure loss,
ΔT=3K*
kPa
203
89**
127
229
141
Flow, ΔT=4K*
l/s
1.24
1.64
2.56
3.39
5.04
Max. allowed external pressure loss, ΔT=4K* kPa
208
100**
152
244
197
*ISO 14511.
**The maximum allowed external pressure loss in the brine circuit can be increased to the value 191 kPa
ΔT3, (204 ΔT4) by using a 35 A fuse. More information is available from your local dealer.
66 (75)
M8010 2204EN
Summary of Contents for ESi 6-17
Page 2: ......
Page 62: ...Dimensional drawings ESi 10ESI14_2 ESI 1 ver 1 10ESI14_2 ESI 2 ver 1 60 75 M8010 2204EN...
Page 63: ...Dimensional drawings EMi 10EMI28T_3 EMI ver 1 M8010 2204EN 61 75...
Page 64: ...Dimensional drawings ELi 10ELI60T_2 ELI ver 1 62 75 M8010 2204EN...
Page 78: ...76 75 M8010 2204EN...
Page 79: ......