DIAM3100©2012 AUGIER SA.
IV-52
Symptom
Fault
Action
“WARNING : LFD level 1
”
“WARNING : LFD level 2
”
Possible output regulated current
instability.
Possible loss of CAT conditions.
Replace burnt lamps.
Check warning thresholds.
Perform function learning again.
“WARNING : Meas. lamps
”
No output voltage measurement.
Inconsistent measure.
Check wire position in current sensor
for proper current direction, using
ALIZE4100 (“graphic” display, all
curves must be phased)
Perform “lamp burnt” learning again.
“ALARM : BAD Interface
”
No remote control
Check
remote
control
board
connexions.
Replace
remote
control
board.
Check mother board.
“WARNING : BAD Freq.
”
CCR stops for internal protection.
Check supply network.
Frequency out of range or
asymmetrical wave shape.
“WARNING : TC-TS board
”
No multiwire remote control
Replace relay remote control board.
“WARNING : Power Drop
”
None for the CCR
More than 10% output power
losses.
FAA : informative warning
“WARNING : Temp. level 1
”
“FAULT : Temp. level 2
”
Main transformer overheat.
AENA: Check environmental
conditions.
«ALARM : BAD SUPPLY»
CCR stops or does not start
Check supply network voltage, CCR
nominal voltage setting (see
“configuration” menu) or input
voltage measurement (see
“Supervision” menu).
Refer to chapter I.5.3.1
Summary of Contents for AUGIER energy DIAM3100 Series
Page 2: ...DIAM3100 2012 AUGIER SA I 2...
Page 6: ...DIAM3100 2012 AUGIER SA I 6...
Page 13: ...DIAM3100 2012 AUGIER SA I 13 I 2 4 DIMENSIONS...
Page 14: ...DIAM3100 2012 AUGIER SA I 14 Stacked CCRs...
Page 28: ...DIAM3100 2012 AUGIER SA I 28...
Page 56: ...DIAM3100 2012 AUGIER SA V 56 V APPENDIX A DIAGRAM...