DIAM3100©2012 AUGIER SA.
III-44
III
COMMISSIONING
After that all installation operations defined in the previous section have been completed, the DIAM3100
CCR can be commissioned.
III.1 PROCEDURE
1.
Set the tapping as shown in § II.3.1
2.
Close the fuse box master switches
3.
Close the front panel of the DIAM3100
4.
Switch on the power to installation
The display light up:
5.
Set the IP address of the CCR, as shown in II.2.2.2
6.
Press
local
button, the display seems to:
The CCR starts up and the output current is displayed on the front panel.
7.
Progressively increase the brightness levels using the selection buttons while systematically checking
the current value shown by the numeric display, maximum brightness being fixed at 6.6A.
8.
Decrease the brightness levels again, then stop the CCR by pressing
stop
button
If the CCR does not supply the desired current, see paragraph IV.3.2.4
9.
Check operation of the CCR in remote control mode. (Press
auto
button )
Io:0.00A STOP
stop
local
auto
menu
Io:1.50A <B0>
stop
B-
B+
menu
Summary of Contents for AUGIER energy DIAM3100 Series