DIAM3100©2012 AUGIER SA.
II-36
Serial link parameters:
The asynchronous serial links are defined as follows:
Preferred parameters : 9600 baud, 8 data bits, 1 stop bits, no parity.
JBUS protocol with Id=1 at delivery.
It is possible to change the speed and the ID in the “
Serial Link”
menu:
•
Speed:
2400-4800-9600-19200
Baud
•
ID:
1 to 249
These changes are active after a device reset (mains disconnection).
The 2 serial links access to the same jbus table with the same priority (the last order is the one taken).
Communication (for the link 1 or 2) is shown on the display, by mean of 2 arrows Rx & Tx :
Rx
Tx
The JBUS table is defined in appendix b: jbus table