DIAM3100©2012 AUGIER SA.
II-31
II.1.5 CHECKING THE INSTALLATION
Checking the suitability of the electrical installation in which the CCR is to be integrated, the following
points must be observed:
II.1.5.1 Single phase power supply :
This must be compatible with the electrical characteristics of the device as shown on the rating plate and
factory test report.
The rated mains voltage is recorded in the software on the motherboard and is required for calculations.
The configured rated voltage can be seen in the “
Configuration
” menu, and written on the identification
plate, on the front panel.
See paragraph I.3.3 for the electrical characteristics of DIAM CCRs.
II.1.5.2 LV Protection :
The LV protection for each CCR from the mains must be proportioned according to the power of the CCR,
the rated voltage and the type of protection already present on the CCR.
The following tables are given for information only, for cable lengths between fuse boxes and CCRs of less than
30m (Circuit breaker examples : MG references)
220 to 240V Power Supply
380 to 415V Power Supply
Power
LV cable gauge
LV circuit breaker
LV cable gauge
LV circuit breaker
1KVA
6 mm²
IC60N 20A D
4 mm²
IC60N 16A D
2.5KVA
6 mm²
IC60N 25A D
6 mm²
IC60N 20A D
4KVA
10 mm²
IC60N 40A D
6 mm²
IC60N 25A D
5KVA
16 mm²
IC60N 50A D
10 mm²
IC60N 32A D
6.5 kVA
16 mm²
IC60N 63A D
10 mm²
IC60N 40A D
II.1.5.3 Lighting loop :
Check that the installed power corresponds to the power of the CCR, check the continuity of the loop and
the number of lamps blown.
The rated output power is recorded in the software on the motherboard and is required for calculations.
The configured rated p
ower can be seen in the “
Configuration
” menu
II.1.5.4 Control by remote control :
Check the remote control mode using ETHERNET, RS485 or SOURIAU link.
See paragraph I.3.3 for the electrical characteristics of the DIAM3100 CCRs.
Summary of Contents for AUGIER energy DIAM3100 Series
Page 2: ...DIAM3100 2012 AUGIER SA I 2...
Page 6: ...DIAM3100 2012 AUGIER SA I 6...
Page 13: ...DIAM3100 2012 AUGIER SA I 13 I 2 4 DIMENSIONS...
Page 14: ...DIAM3100 2012 AUGIER SA I 14 Stacked CCRs...
Page 28: ...DIAM3100 2012 AUGIER SA I 28...
Page 56: ...DIAM3100 2012 AUGIER SA V 56 V APPENDIX A DIAGRAM...