Control Systems
OBR Control Systems Inc
OBR Control Systems Inc
Telephone : +1 (248) 672-3339
32233 West 8 Mile Road
www.obrcontrolsystems.com
Livonia, Michigan 48152
USA
18 / 92
- Tri-state outputs
- Wipers
- Event Flash
- Event Delay On
- Event Delay Off
5.3.6 Time (ms)
Set the On and OFF timers for use with these functions:
- Flash
- Delay Input On
- Delay Input Off
5.3.7 CAN Inputs – Lost CAN Action
For safety reasons it is possible to set conditions for channels controlled via CAN.
If the CAN bus communication is lost at any time for a defined time interval (in milliseconds) the
following actions can be defined, individually for each CAN invent:
- Do nothing (keep current status)
- Turn Off (switch the output off when the CAN lost timer expires)
- Turn On (switch the output on when the CAN lost timer expires)
5.3.8 CAN Lost Timer
This defines a time interval for receiving CAN messages. If a given CAN message is not updated
within the time interval, the system considers the CAN bus has gone into fault mode.
DO NOT SET THIS INTERVAL TO 0 (ZERO)!
It is recommended to use an interval of app. 2.5 times the message update rate. For example, if
the update interval is 100 msec, it is recommended to set the time interval to 250 msec. During this
time interval the system should recognise 2 messages, confirming the CAN bus is functioning.
Select which output this event controls.
Select NONE if this is a conditioning event which is part of a logic switch string.
It is essential that only one (1) event controls a given output. If multiple switching conditions apply,
these must be joined in a single, final event, for example an AND, OR etc event,
5.3.9 Start State
Use this function to define whether a flash function starts having the output switched ON or OFF.
5.3.10
Output
Select an output to be triggered by the event. If the actual event is a conditional event, no output is
selected.
5.3.11
Multiplier
Not in use in this software release.
5.3.12
Counter
Refer to sections 5.3.1.11, 5.3.1.12 and 5.6 for a description of the counter features.
Select a configured counter to use with the Counter event.
5.3.13
Clock
This feature is used with the Clock event.
Set time for switching On and set a time for switching Off.
Click “Save” to save the event configuration.
Click on the “Visualise” button to open the visualisation display. See section 8.