5.8
Electrical Settings
5.8.1
Trace Current
Figure 101 - Trace Current Settings for 1-Phase Heat Trace Circuit
This page displays the live value of the Trace Current associated with a heat trace circuit.
5.8.1.1 High/Low Trace Current Alarm Settings
Figure 102 - High/Low Trace Current Alarm Settings
Procedure:
Touch an
Enable
check box to turn on/off the corresponding Alarm. Touch the corresponding
Latch
check box to select a latching or a non-latching alarm type. When
Latch
is selected, the alarm will to be
manually reset each time the corresponding alarm occurs.
Figure 103 - High/Low Trace Current Setpoint & Filter Settings
Filter
: When the current exceeds the High Current Setpoint or drops below the Low Current Setpoint,
the controller will only trigger an alarm if the corresponding High/Low alarm condition is present for the
duration of the filter period (0 - 28 seconds). If an immediate alarm output is required when an alarm con
-
dition occurs, then the corresponding filter value should be set to 0.