nVent RAYCHEM Elexant 4010i/4020i User Manual
RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905
nVent.com
|
66
5.6.7.6 Heater on Time
Figure 89 - Heater on Time Setting
Range:
1 to 250,000 hours
Default:
100000
Purpose:
This generates an alarm if the Heater ON time reaches or exceeds the set number of operational hours.
Default:
Enabled and set at 100,000 hours.
5.7
Temperature Settings Page
This page provides access to the selection and settings of Temperature Sensor (x) and to Temperature
Limiting features.
Figure 90 - Temperature Settings Page
5.7.1
Temp Sensor (x) Reading
Purpose:
This temperature is the value that the controller is reading from the temperature sensor connected to
the corresponding temperature sensor input. Depending on the TS Control Mode, it may be used to
determine the Control Temperature.
IMPORTANT:
If the sensor device is not connected to the device at the terminal block, the TS(x) input
reading is displayed as N/A