Purpose:
When “Control” is selected, the alarm settings for the Temperature Sensor can be configured using the
lower half of the page as shown above.
Procedure:
Touch the corresponding
Enable
check box to turn on/off the corresponding Alarm indication and
touch the corresponding
Latch
check box to define a latching or a non-latching type. When the Latch is
selected, the alarm will need to be manually reset each time the corresponding alarm occurs.
Figure 97 - Filter Setting
Filter
: When the temperature exceeds the High Temperature Setpoint or drops below the Low
Temperature Setpoint, the unit only triggers an alarm if the corresponding High/Low alarm condition is
present for the “Filter” period. If immediate alarm output is required for an alarm condition, then the
corresponding filter value should be set to 0.
Alarm Setpoint
Description
Default
Value
Range
Filte
(seconds)
High Temperature
This alarm is active when the sen-
sor temperature has surpassed
the value of the High Temperature
Setpoint.
100°C
-200°C to 700°C
0 to 59940
Low Temperature
This alarm is active when the sen-
sor temperature is below the value
of Low Temperature Setpoint.
5°C
-200°C to 700°C
0 to 59940
Failure
This alarm is active when the tem-
perature sensor has failed.
N/A
N/A
N/A
Table 22 - Temperature Alarm Settings
5.7.2
Temp Limiting
Figure 98 - Temp Limiting Settings Page