2.6.16 AUX 24V Output
The 24V DC output (terminals 1, 4 of TB3) may be used to connect peripheral equipment, if required. The
Aux 24V output has a rating of 24Vdc, max load of 250mA @ 40°C, de-rated to 165mA @ 60°C.
Figure 23 - AUX 24V Output
2.6.17 Limiter Relay Output
When using optional Limiter variants, the Limiter Relay output (Terminal 2 of TB3) drives an external
limiter contactor coil. Note that this is a wet contact, and provides an output voltage derived from the
incoming module power. The Limiter contactor is placed in line with the load connections to ensure that
when the Limiter has tripped, the Limiter contactor will interrupt the power to the load heating circuit.
See Chapter 4.1 for detailed description of limiter functionality.
Note:
Limiter Relay Output is not available on Elexant 4010i units.
Figure 24 – Elexant 4020i - Limiter Relay Connections