nVent RAYCHEM Elexant 4010i/4020i User Manual
RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905
nVent.com
|
91
5.14 User Interface Settings
Figure 152 - User Interface Settings
This page allows the user to configure the unit to their personal preferences.
5.14.1 Language
Figure 153 - Language Setting
Purpose:
This field allows the user to change the language of the Graphical User Interface (GUI).
Options:
English, French, German, Spanish and Russian.
Default:
English
5.14.2 Temperature Units
Figure 154 - Temperature Unit Setting
Purpose:
This field allows the user to change the units used to display temperatures on the
controller GUI.
Options:
Degrees Celsius (°C), Degrees Fahrenheit (°F)
Default:
Degrees Celsius (°C)
5.14.3 Passcode
Figure 155 - Passcode Setting
Purpose:
This is a four-digit, numeric field to stop unauthorized users from modifying the controller’s
configuration parameters using the touch screen.
Range:
0000 to 9999
Default:
0000
Procedure:
Touch the Passcode field and enter the desired passcode using the numeric keypad. A passcode of 0000
disables the lockout feature and allows all configuration parameters to be modified using the operator
console without requiring a passcode. Setting the passcode to any other value will require the database
to be unlocked by entering the correct passcode prior to modifying any of the controller’s configuration
parameters using the touch screen.