nVent RAYCHEM Elexant 4010i/4020i User Manual
RAYCHEM-AR-H60624-40X0iOpsManual-EN-1905
nVent.com
|
75
intended design, which can cause significant loss of/excess heater output.
5.8.3.1 High/Low Trace Voltage Alarm Settings
Procedure:
Figure 112 - High/Low Trace Voltage Settings
Touch the corresponding
Enable
check box to turn on/off the corresponding Alarm indication and touch
the corresponding
Latch
check box to select a latching or a non-latching alarm type. When latching is
selected the alarm will need to be reset manually each time the corresponding alarm has occurred.
Figure 113 - High/Low Trace Voltage Setpoint & Filter Settings
Filter:
When the voltage exceeds the High Voltage Setpoint or drops below the Low Voltage Setpoint, the
unit only triggers an alarm if the corresponding High/Low alarm condition is present for the duration of
the filter period (0 - 28 seconds). If an immediate alarm output is required, then the corresponding filter
value should be set to 0.
Value
Description
Default Value Range
Trace Voltage High -
Setpoint
This alarm is generated when the voltage being
monitored exceeds the defined High setpoint.
300 V
80 V to 300 V
Trace Voltage Low -
Setpoint
This alarm is generated when the voltage be
-
ing monitored drops below the defined Low
setpoint.
90 V
80 V to 300 V
Table 26 - High/Low Trace Voltage Alarm Settings
Figure 114 – 3 Phase Trace Voltage Page