8. External Interfaces
8.1. Stack Switchgear
8.1.1. Battery Stack and DC Bus
The connectors use #M8 screws (included) and are intended for #M8 lugs (not included, e.g. Panduit
Corp LCMA50-8-L).
Flexible snap-on terminal covers are included. The maximum acceptable terminal lug tongue width is
1.1 inches and the maximum wire size is 4/0.
The recommended tightening torque is 5.7 to 6.8 N-m [50 to 60 in-lbs].
Table 13. Battery Stack and DC Bus Connector Assignment
Name
Description
Connected to Device
Battery (-)
Negative terminal of battery stack
Battery stack
Battery (+)
Positive terminal of battery stack
Battery stack
DC Bus (-)
Negative terminal of DC bus
External equipment
DC Bus (+)
Positive terminal of DC bus
External equipment
8.1.2. Ethernet
The Ethernet jack is a standard RJ45 Cat5e rated jack.
Table 14. Ethernet Connector Pin Assignment
Pin
Connection
Description
Connected to Device
1
TD_P
Transmit differential pair positive
External Equipment
2
TD_N
Transmit differential pair negative
External Equipment
3
RD_P
Receive differential pair positive
External Equipment
4
NUL45
Unused; connected to Pin 5 and terminated
External Equipment
5
NUL45
Unused; connected to Pin 4 and terminated
External Equipment
6
RD_N
Receive differential pair negative
External Equipment
7
NUL78
Unused; connected to Pin 8 and terminated
External Equipment
Nuvation Energy High-Voltage BMS - Product Manual
Document ID: NE-PM-003
71
Rev 1.2, 2021-03-03
Curie Update 1