provides a decent medium to couple system noise into the Link Bus which can result in
sc_linkbus
communication faults.
In systems where the cells can provide the necessary minimum operating voltage to the Cell
Interface, Link Bus power can be disabled if the observed impact on performance is acceptable. The
power twisted pair must be disconnected in the Link Bus cable, so all Link Out and Link In connectors
on the Stack Switchgear and the Cell Interface modules must have pins 1 and 2 unpopulated.