Environmental Conditions
Symbol
Parameter
Min
Typ
Max
Units
Thermal Specifications
T
a
Operating Temperature
-10
25
60
°C
Storage Temperature
-20
25
60
°C
Humidity Specifications
RH
Operational RH
5
-
85
%
Storage RH
5
-
85
%
Shock and Vibration Specifications
Vertical
Vertical shock/vibration
-
-
10
m/s
2
Longitudinal
Longitudinal shock/vibration
-
-
10
m/s
2
Transverse
Transverse shock/vibration
-
-
10
m/s
2
Pulse vibration
On each axis
-
-
245
m/s
2
The Cell Interface has been designed to meet the requirements of SAE J2464 (shock) and SAE J2380
(random vibration).
Standards and Certifications
The Cell Interface meets industry standards CISPR 22 Class A and IEC/EN 61000-4-2 for EMC/EMI
and ESD respectively. It has been designed to meet EN 60950 high voltage creepage/clearance
distances for reinforced insulation rated to 1250 V DC. All components are EU RoHS / China RoHS
compliant.
Standard/Certification
Stationary Battery Safety
UL Recognized
UL 1973 (file no. MH64071)
Functional Safety
UL Recognized
UL 991 (file no. MH64071)
UL 1998 (file no. MH64071)
UL 1973 recognition ensures safe battery operation and significantly reduce the effort of certifying the
energy storage solution to meet UL 1973 and UL 9540.
Maximum Stack Deployment
Cell Interface modules are deployed as a daisy chain to monitor the cells of a stack. The maximum
number of modules that are supported in a stack depend on two metrics:
▪
the maximum number of modules that can be powered over Link Bus power (if required)
▪
the required scan rate of the cell voltage measurements
Limits Due to Link Bus Power
Max CI-12
Max CI-16
Max CI-4M12
50
40
40
Nuvation Energy High-Voltage BMS - Product Manual
Document ID: NE-PM-003
96
Rev 1.2, 2021-03-03
Curie Update 1