Appendix A: Operating Limits
Stack Switchgear
Exceeding the ratings will damage the system.
External Specifications
Symbol
Parameter
Min
Typ
Max
Units
V
input
Input Voltage
100
-
240
V AC
I
input
Input Current
0.6
1.1
1.3
A AC
P
input
Input Power
-
33.7
60
W
f
input
Input Frequency
45
50/60
65
Hz
V
fan_DC
Cooling Fan DC Voltage
-
-
50
V DC
V
fan_AC
Cooling Fan AC Voltage
-
-
250
V AC
I
fan
Cooling Fan Current
-
-
5
A DC/AC
I
E-Stop
E-Stop Input Current Rating
-
-
9.6
mA DC
V
E-Stop
E-Stop Input Voltage Rating
19.2
24
28.8
V DC
Electrical Characteristics
Symbol
Parameter
Min
Typ
Max
Units
Stack Switchgear Configuration: 1250 V DC, XXX A
*
V
stack_ov
Stack Over-Voltage Threshold (contactors open)
0
Configurable
1250
V DC
V
stack_uv
Stack Under-Voltage Threshold (contactors open)
0
Configurable
-
V DC
I
discharge_oc
Stack Discharging Over-Current (contactors open)
0
Configurable
XXX
A DC
I
charge_oc
Stack Charging Over-Current (contactors open)
0
Configurable
XXX
A DC
Battery Cell Specifications
C
ov
Cell Over-Voltage Threshold (contactors open)
-
Configurable
-
V
C
uv
Cell Under-Voltage Threshold (contactors open)
-
Configurable
-
V
Temperature Sensors Specifications
T
ut
Under-Temperature Threshold (contactors open)
-
Configurable
-
°C
T
ot
Over-Temperature Threshold (contactors open)
-
Configurable
-
°C
T
fan_en
Fan Enable Temperature Threshold
-
Configurable
-
°C
* The current configurations available are as follows:
▪
100 A
▪
200 A
▪
300 A