OPERATOR & MAINTENANCE MANUAL
22
③
Connect the wires between the mains supply wiring terminals
and the ATS wiring terminals.
④
Connect the wires between the load wiring terminals and the ATS wiring terminals.
Warning:
Do not operate the generator before connection of the ATS.
The ATS is controlled by the PLC module which can monitor the incoming AC mains supply.
If the mains power supply is within tolerance the load is run through the ATS and the
generator will not run. If the mains power supply is not within tolerance the generator will
run.
The ATS location is important
The ATS should be located inside the building as close as possible to the main switch
board.
Locate the ATS in a clean, dry, well ventilated location, away from excessive heat. If
the ambient temperature is above 40°C (104°F), fuses and circuit breakers must be
de-rated. Allow adequate working space around the transfer switch.
Never install control wiring in the same conduit as power wiring.
The ATS and all equipment must be installed in accordance with relevant local and
national codes and regulations.
If the ATS is mounted outside, it must be protected from the environment.
Do not mount the ATS on the generator.
Do not mount the ATS where flammable liquids or vapours are present.