OPERATOR & MAINTENANCE MANUAL
28
5.6 Stopping Generator under Manual Operation Mode
①
Turn off every Circuit Breaker.
②
Turn the Main Circuit Breaker (2) to “OFF” position.
③
Press the OFF button (c)
④
Allow the engine to idle for approximately one minute to cool down.
⑤
Turn off the Key Switch (7) .
⑥
Open the side access door and turn off the engine battery switch, then close the door.
5.7 Stopping Generator under Automatic Operation Mode
If the mains supply returns and the generator does not stop running, follow the steps
listed below :
①
Turn every switch and circuit breaker on the load to the “OFF” position.
②
Turn off the Key Switch (7) .
③
Open the side access door and turn off the engine battery switch, then close the door.
5.8 Protection
5.8.1 Displaying alarm signals
The control module (PLC) has 3 ways of displaying alarm signals if a fault occurs.
①
The audible alarm will sound for ten seconds. If you want to silence the alarm, press
the Mute button (u) .
②
The Alarm LED (x) illuminates. If LED illumination is steady, it means the
alarm is acknowledged. On the contrary the flashing LED indicates an
unacknowledged alarm.
③
The LCD (y) can display the appropriate alarm text.