OPERATOR & MAINTENANCE MANUAL
27
5.4 Automatic Start-up
①
Follow steps
①
to
④
as described in section 5.3.
②
Turn the ATS (automatic transfer switch) to “AUTO” position.
③
Press the Auto button (l) , then the LED above the button will illuminate. The
module will proceed with its normal auto start sequence.
④
The module will monitor the incoming AC mains supply. If the mains supply is within
the preset tolerances, the ATS will carry the mains loads and the generator will not run.
On the contrary the generator will supply power if the mains supply is outside the preset
tolerances.
⑤
The generator will operate up to 5 seconds (Warm up Mode).
⑥
PLC will automatically switch (ATS) load circuit breaker to “ON” and the generator will
supply power.
Note: Before operating the automatic start-up mode, connection of ATS is required.
5.5 During Operation
Check the LCD reading of voltage, current, frequency by scrolling the
Display Button (w) , and (v)
Check the LCD reading of engine oil, coolant and fuel levels.
Check the LCD reading of engine oil pressure and coolant temperature.
Check for any alarm signal on the LCD or audible alarm.
Check for any leakage of coolant, oil or fuel.
Check for any unusual vibration or noise.
Check for any unusual colour from the exhaust. Under normal conditions the exhaust
gas has no colour.
If the engine cannot run because of low fuel, bleed the air
from the fuel system.
Loosen air release bleed bolt on the fuel filter.
Bleed the air in the fuel system for about 30
seconds.
Tighten the bolt.
Caution:
If a fault is detected, stop and isolate the machine immediately. The generator is only to
be repaired by certified or fully trained personnel (refer troubleshooting guidelines 6.7).