46
XBOXER XBC
ECOSMART (CO) MODELS
12.0 ELECTRICAL DETAILS
12.6 CONNECTION CHART
Description
Controller
Din Rail
Relay
Terminal No
Terminal No
DI
AI
Output
AO
Fresh Air Sensor
IN 1
1
Supply Air Sensor
IN2
1
Return/Room Air Sensor
IN3
25-26
1
Input 4
IN4
1
Input 5
IN5
31-32
1
Alarm Circuit 1 (Fan, Heater)
IN6
27-28 (Some Models)
1
Alarm Circuit 2 (Pump, Filter)
IN7
29-30
1
Volt-Free Enable Input Signal
IN8
33-34
1
Volt-Free Boost Input Signal
IN9
35-36
1
Extract Fan 0-10V
OUT1
1
Supply Fan 0-10V
OUT2
1
Heat Demand 0-10V
OUT3
1
Cool Demand 0-10V
OUT4
1
Bypass Damper Relay
OUT5
1
Volt-Free Healthy Relay
OUT6
1
Volt-Free Fan Run Relay
OUT7
1
Volt-Free Cool Demand Relay
OUT8
1
Volt-Free Heat Demand Relay
OUT9
1
230V Enable Input
10
1
230V Fan Boost Input
11
1
(MS/TP)
Summary of Contents for ecosmart CONNECT XBOXER XBC
Page 51: ...51 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 52: ...029 2085 8200 52 XBOXER XBC ECOSMART CO MODELS Figure 35 13 0 DIAGRAMS 13 4 PHYSICAL LAYOUT...
Page 53: ...53 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 55: ...55 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 57: ...57 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 59: ...59 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...
Page 61: ...61 nuaire co uk XBOXER XBC ECOSMART CO MODELS 30 11 15 Leaflet Number 671710...